Cooling and compressor room

How much air removes heat from the compressor room?

Determine ventilation from the heat that actually remains in the room, not automatically from motor power.

Your inputs

Example data – these are not your operating figures. Adjust them before calculating.

Result

Enter your inputs and run the calculation. See the result immediately, without registering or providing an email address.

How we calculate

Method: Qair = Pheat / (ρ × cp × ΔT), cp = 1005 J/(kg·K), ρ = p/(RT) at the inlet temperature and 1.01325 bar abs.

Assumptions and limitations: Steady state, perfect mixing, no heat storage or solar gains. Add actual additional heat gains. The flow does not size a fan: resistance, replacement air supply and manufacturer requirements must be checked.

Method references
  • KAESER: Compressed Air System Installation Guide – ventilation and separation of cooling exhaust air.

Method version 1.0. Standard references verified in the ISO catalogue; the physical balances are not calculations prescribed by ISO. Before final design, we will verify actual operating and catalogue data.